Wire gauge & fuse calculator

At 12 V a 3 % voltage-drop budget is only 0.36 V, so on van-length runs the drop — not the current — usually decides your cable. This sizes for both and tells you which one governed.

Battery to appliance. The return leg is added for you.

Recommended cable

3.31 mm² (12 AWG)

Fuse

15 A

Voltage drop

0.32 V (2.7 %)

Round-trip length

6.0 m

Voltage drop set this size.

Planning figures, not certification. Standards are summarised for builders; your inspector, your van's plate and your own measurements always win.

How this is calculated

  1. Cross-section from the drop budget: A = ρ × L × I ÷ V_drop, with ρ = 0.0178 Ω·mm²/m for warm stranded copper and L the round-trip length (both conductors).
  2. Ampacity from ABYC E-11 for 105 °C insulation outside engine spaces, up to three bundled conductors. The thicker of the two requirements is the recommendation.
  3. Fuse at 1.2 × the continuous load, rounded up to a size that is actually sold, and never above the cable's ampacity — the fuse protects the wire, not the appliance.

Sources

  • ABYC E-11 — AC & DC electrical systems on boats (the ampacity table the van world borrows)
  • Explorist.life — wire sizing and fuse sizing guides
  • FarOutRide — van electrical system guide