Wire gauge & fuse calculator
At 12 V a 3 % voltage-drop budget is only 0.36 V, so on van-length runs the drop — not the current — usually decides your cable. This sizes for both and tells you which one governed.
Battery to appliance. The return leg is added for you.
Recommended cable
3.31 mm² (12 AWG)
Fuse
15 A
Voltage drop
0.32 V (2.7 %)
Round-trip length
6.0 m
Voltage drop set this size.
Planning figures, not certification. Standards are summarised for builders; your inspector, your van's plate and your own measurements always win.
How this is calculated
- Cross-section from the drop budget: A = ρ × L × I ÷ V_drop, with ρ = 0.0178 Ω·mm²/m for warm stranded copper and L the round-trip length (both conductors).
- Ampacity from ABYC E-11 for 105 °C insulation outside engine spaces, up to three bundled conductors. The thicker of the two requirements is the recommendation.
- Fuse at 1.2 × the continuous load, rounded up to a size that is actually sold, and never above the cable's ampacity — the fuse protects the wire, not the appliance.
Sources
- ABYC E-11 — AC & DC electrical systems on boats (the ampacity table the van world borrows)
- Explorist.life — wire sizing and fuse sizing guides
- FarOutRide — van electrical system guide